Dwyer UXF3 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Accessoires d'air Dwyer UXF3. Dwyer UXF3 User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 73
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Robert Thompson
FIXED TYPE ULTRASONIC
FLOWMETER
COMMUNICATION
FUNCTIONS
TYPE: UXF3
Instruction Manual
Dwyer Instruments, Inc.
Bulletin F-107-UXF3-S
Vue de la page 0
1 2 3 4 5 6 ... 72 73

Résumé du contenu

Page 1 - FUNCTIONS

Robert ThompsonFIXED TYPE ULTRASONIC FLOWMETERCOMMUNICATION FUNCTIONSTYPE: UXF3Instruction Manual Dwyer Instruments, Inc.Bulletin F-107-UXF3-S

Page 2

- 6 - 3.2.2 RS-232C interface 15 m or less Master(PC) Slave(UXF3)CD 1 4 TXD RXD 2 3 RXD TXD 3 2 GND DTR 4 1 DI1 GND 5 DSR 6 RTS 7 CTS 8 CI 9

Page 3 - CONTENTS

- 7 - 4.SETTING OF COMMUNICATION CONDITIONIn order that the master station and instrument (this instrument) can correctly communicate, following setti

Page 4

- 8 - 5. MODBUS COMMUNICATION PROTOCOL 5.1 General The communication system by the MODBUS protocol is that the communication is always started from t

Page 5 - 1. COMMUNICATION FUNCTIONS

- 9 - 5.2 Composition of Message Command message and response message consist of 4 fields ; Station No., Function code, Data and Error check code.

Page 6

- 10 - 5.3 Response of Slave Station (1) Response for normal command To a relevant message, the slave station creates and sends back a response mess

Page 7 - 2. SPECIFICATIONS

- 11 - 5.4 Function Code According to MODBUS protocol, register numbers are assigned by function codes. Each function code acts on specific register n

Page 8 - 3. CONNECTION

- 12 - 5.5 Calculation of Error Check Code (CRC-16) CRC-16 is the 2-byte (16-bits) error check code. From the top of the message (station No.) to

Page 9 - 3.2 Wiring

- 13 - 5.6 Transmission Control Procedure (1) Transmission procedure of master station The master station must proceed to a communication upon confor

Page 10 - 3.2.2 RS-232C interface

- 14 - POL1POL2POL1 POL2 POL1 response dataPOL1 response dataSpace time of longer than 25 ms is needed.5 to 60 ms Masterstationĺ UXF3Masterstationĸ UX

Page 11 - 4.1 Set Items

- 15 - 5.7 FIX Processing (Cautions in data write) The instrument is provided inside with a non-volatile memory (Fe-RAM) for holding the setting para

Page 12 - 5.1 General

Note: MODBUS® is the trademark or registered trademark of AEG Schneider Automation International. NOTICEThe contents of this document may be changed

Page 13 - 5.2 Composition of Message

- 16 - 6. DETAILS OF MESSAGE 6.1 Read-out of Word Data [Function code:03H]Function code Max. word number read-out in one message Relative data addre

Page 14 - Table 5-1 Error Code

- 17 - (3) Message transmission (example) Reading “Damping” from No. 2 station is shown below. Relative address of damping: 0000H(Register No.40001),

Page 15 - 5.4 Function Code

- 18 - 6.2Read-out of Read-out Only Word Data [Function code:04H]Function code Max. word number read-outin one message Relative data address Register

Page 16 - Bulletin F-107-UXF3-S

- 19 - (3) Message transmission (example) The following is an example of reading out the flow rate from station No. 1. Relative address of the flow r

Page 17 - (2) Description

- 20 - 6.3 Write-in of Word Data [Function code:06H]Function code Max. word number write-in in one message Relative data addressRegister No. Kind of

Page 18

- 21 - 6.4 Write-in of continuous word data [Function code:10H]Function code Max. word number write-in in one message Relative data addressRegiste

Page 19 - Cautions:

- 22 - (3) Message transmission (example) Writing Flow unit = m3/h, Range type = single range, Full scale 1 = 300.0 m3/h in No. 1 station is shown be

Page 20 - 6. DETAILS OF MESSAGE

- 23 - 7. ADDRESS MAP AND DATA FORMAT 7.1 Data Format 7.1.1 Transmission data format The MODBUS protocol used in this product is RTU (Remote Terminal

Page 21

- 24 - (3) 64-bit floating data (double type)Instantaneous values or the like are expressed by 64-bit double precision float type. The meaning of each

Page 22

- 25 - 7.2 Address Map See the instruction manual attached to the main unit for details of functions and setting ranges of individual parameters. Dat

Page 23

㧙i㧙CONTENTS1. COMMUNICATION FUNCTIONS ...11.1 Gener

Page 24

- 26 - RelativeaddressRegister No. Datatype Parameter Read-out data/Write-in data setting range Remarks 0042 40067 int Total mode 0: Start, 1

Page 25

- 27 - RelativeaddressRegister No. Datatype Parameter Read-out data/Write-in data setting range Remarks 00C6 40199 int Decimal point position

Page 26

- 28 - RelativeaddressRegister No. Datatype Parameter Read-out data/Write-in data setting range Remarks 0106 40263 int Transmission count Normal

Page 27 -  127 = 1

- 29 - The address data indicated below is not stored in the main unit. RelativeaddressRegister No. Datatype Parameter Read-out data/Write-in data

Page 28 -  1023 = 0

- 30 - 7.2.3 Word data [Read-out only]: Function code [04H] RelativeaddressRegister No. Datatype Parameter Read-out data/Write-in data setting ra

Page 29 - 7.2 Address Map

- 31 - RelativeaddressRegister No. Datatype Parameter Read-out data/Write-in data setting range Remarks 0084 30133 unsignedintSensor spacing 2 N

Page 30

- 32 - 8. COMMUNICATION PROTOCOL 8.1 General The communication system by this protocol is that the communication is always started from the master st

Page 31

- 33 - 8.2 Message Configuration 8.2.1 Reception Description Bytes Remarks Start mark 1 : (3Ah) Slave address (SLV) 2 01 to 31 Function code (F_C

Page 32

- 34 - 8.4 Function Code Table Description F_CD Remarks Flow velocity 0300 Flow rate 0310 Forward integrated value 0320 Reverse integrated va

Page 33

- 35 - 9. PC LOADER SOFTWARE IN CD SUPPLIED WITH THE MAIN UNIT 9.1 Copyright of This Software The copyright of this software belongs to the manufact

Page 34

㧙ii㧙9.12 System Setting...

Page 35

- 36 - 9.4 Installing of Software (1) Insert the setup disk into the drive, and double-click “UltrasonicFlowmeter_eng.msi.” Fig. 9-1 <Install fil

Page 36 - 8. COMMUNICATION PROTOCOL

- 37 - (3) There is a query about selection of installation folder. Click the [Next] button to install the software in that folder. To specify

Page 37 - 8.3 Error Check

- 38 - (5) Execution of Installation Fig. 9-5 < Installing screen > (6) The Installation Complete screen is displayed. Click the [Close] bu

Page 38 - 8.5 Error Code Table

- 39 - 9.5 Startup Method Start “Ultrasonic Flowmeter” from the start menu or the shortcut menu to start up the loader. Fig. 9-7 < Start screen >

Page 39 - SUPPLIED WITH THE MAIN UNIT

- 40 - 9.5.1 Communications Click “Communication” on the menu bar on the Menu screen, and the following setup screen appears. Fig. 9-9 < Serial com

Page 40 - 9.4 Installing of Software

- 41 - 9.5.2 Setting Click “Setting” on the menu bar on the Menu screen, and either “Save setting” or “Read setting” can be selected. 9.5.2.1. Save

Page 41

- 42 - 9.5.3 Calculation Sensor Spacing On the menu screen, click [Calculation Sensor Spacing] of the menu bar, and the following screen appears. Thi

Page 42

- 43 - 9.5.4 Version Click “Version” on the menu bar on the Menu screen, and the following screen appears. Fig. 9-13 < Version screen > Click th

Page 43 - 9.5 Startup Method

- 44 - 9.7 Process Setting Click the “PROCESS SETTING” button on the Menu screen, and the following screen appears. Fig. 9-14 < Process setting scr

Page 44 - 9.5.1 Communications

- 45 - [Setting]...Sends the setting of the selected item (check box set to ON (;)), reflecting the response value on the setting.

Page 45 - 9.5.2 Setting

- 1 - 1. COMMUNICATION FUNCTIONS 1.1 General ƒ This instrument provides a communication function by RS-485 interface or RS-232C interface, by which i

Page 46

- 46 - 9.8 Range Setting Click the “RANGE” button on the Menu screen, and the following screen appears. Fig. 9-15 < Range setting screen > To se

Page 47 - 9.6 Structure of Function

- 47 - Table 9-6 < Range Setting > Item Content RANGE UNIT Select from L/s, L/min, L/h, L/d, kL/d, ML/d, m3/s, m3/min, m3/h, m3/d, k m33/d, M m

Page 48 - 9.7 Process Setting

- 48 - 9.9 Total Setting Click the “TOTAL” button on the Menu screen, and the following screen appears. Fig. 9-16 < Total setting screen > To se

Page 49 - Table 9-5 < System >

- 49 - Table 9-11 < Total Setting > Item Content TOTAL MODE Select from TOTAL STOP, TOTAL RUN, TOTAL RESET. TOTAL UNIT Select from mL, L, m3,

Page 50 - 9.8 Range Setting

- 50 - 9.10 Status Output Setting Click the “STATUS” button on the Menu screen, and the following screen appears. Fig. 9-17 < Status output setting

Page 51 - Table 9-7 < Damping >

- 51 - [Check ON/OFF] ...Set the check box to ON to select all the items (to set all the check boxes to ON (;)). Set the check box to OFF () t

Page 52 - 9.9 Total Setting

- 52 - 9.11 Display Setting Click the “DISPLAY” button on the Menu screen, and the following screen appears. Fig. 9-18 < Display setting screen >

Page 53

- 53 - Table 9-14 < Display Setting > Item Content Selection Select from VELOCITY, FLOW RATE, + TOTAL (ACTUAL), – TOTAL (ACTUAL), + TOTAL PULSE

Page 54 - 9.10 Status Output Setting

- 54 - 9.12 System Setting Click the “SYSTEM” button on the Menu screen, and the following screen appears. Fig. 9-19 < System setting screen > T

Page 55

- 55 - 9.13 Measurement Click the “MEASURE” button on the Menu screen, and the following screen appears. Fig. 9-20 < Measure screen > Select Ins

Page 56 - 9.11 Display Setting

- 2 - System configuration (when using the RS-485 interface)RS-485RS-232CPersonalcomputerRS-232C RS-485 converterRS-485ProgrammablecontrollerMas

Page 57

- 56 - Table 9-16 < Measurement/Detailed Setting > Item Content Instantaneous value Select from Flow rate, Flow rate %, and Velocity. Flow rate

Page 58 - 9.12 System Setting

- 57 - 9.14 Transit Time Difference Measurement Click the [TRANSIT TIME] button on the Menu screen, and the following screen appears. Click detail

Page 59 - 9.13 Measurement

- 58 - [Setting]... Sends the setting of the selected item (check box set to ON (;)), reflecting the response value on the setting

Page 60

- 59 - 9.14.2 Received Signal (optional function) Click “RECEIVED SIGNAL”, and the following screen appears. Fig. 9-22 < Received signal screen &g

Page 61 - 9.14.1 Detailed Setting

- 60 - See “Checking send/receive” in “6. Maintenance and Inspection” of the separate instruction manual, “FIXED TYPE ULTRASONIC FLOWMETER” Operation

Page 62

- 61 - Table 9-18 < Operation Information > Item Content WEDGE SOUND VELOCITY m/s [ft/s] WEDGE ANGLE ° PIPE SOUND VELOCITY m/s [ft/s] ANGLE I

Page 63 - Otherwise air is mixed in

- 62 - 9.15 RAS Click the [RAS] button on the menu screen to display the RAS screen shown below. Fig. 9-24 < RAS screen > [READ] button ...

Page 64 - 9.14.3 Operation Information

- 63 - 9.16 Maintenance Click the “MAINTENANCE” button on the Menu screen, and the following screen appears. Note: If [Setting] and [Read] are execut

Page 65

- 64 - Table 9-19 < Maintenance/setting > Item Content AO adjustment When 4mA is selected, without decimal point, Enter in the range from 1 to

Page 66 - 9.15 RAS

- 65 - 9.17 PV Click the [PV] button on the menu screen to display the PV screen (when RS-485 communication system is selected only). CAUTIONx The wi

Page 67 - 9.16 Maintenance

- 3 - 2. SPECIFICATIONS 2.1 Communication Specifications Item Specification Electrical specification Based on EIA RS-485 or based on EIA RS-232C Tran

Page 68

- 66 - [START] button...Starts the measurement of the selected device (;).[Stop] button...S

Page 69 - 9.17 PV

- 67 - 9.18 End Click the [End] button on the Menu screen, and the following screen appears. Fig. 9-27 < Menu screen > Click either the [End] bu

Page 70

- 68 - 10. TROUBLESHOOTING If the communication is unavailable, check the following items.  Whether all devices related to communication are turned

Page 71 - 9.18 End

Corporate Headquarters102 Indiana Highway 212P.O. Box 373Michigan City, IN 46361 U.S.A.Telephone: 219/879-8000Fax: 219/872-9057www.dwyer-inst.comDwye

Page 72 - 10. TROUBLESHOOTING

- 4 - 3. CONNECTION  WARNING To avoid hazard of electric shock and malfunctions, do not turn on the power supply until all wiring has been completed.

Page 73 - INF-TN5A0177-D

- 5 - 3.2 Wiring 3.2.1 RS-485 interface ƒ Use twisted pair cables with shield. Recommended cable: UL2464, UL2448, etc. ƒ The total extension length

Commentaires sur ces manuels

Pas de commentaire