Bulletin F-VFLO
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: [email protected]
Specifications - Installation and Operating Instructions
Venturi Flow Meter with Magnehelic
®
Gage
The Venturi Flow Meter with Magnehelic
®
Gage is fabricated from
aluminum and has a gradual Venturi profile to reduce pressure losses
through the meter. Flexible connections enable the meter to be used in
vertical or horizontal applications. The Magnehelic
®
gage provides a
large, clear and accurate display of your differential pressure reading.
Each meter is calibrated at standard atmospheric conditions. The dual
scale reads in SCFM and in .w.c. The meter is supplied with flow
correction calculation sheet for various flow conditions. It is available in
line sizes from 1˝ to 4˝ and can handle vacuum and pressure
applications.
MOUNTING
Location:
The flow tube should be installed with minimum 8 diameters of pipe run
ahead and 5 diameters of pipe run after. This will ensure steady flow and
accurate readings.
Installation:
1. The meter can be installed in a vertical or horizontal position. The
Magnehelic
®
gage must be positioned such that it is read in a horizontal
orientation. The meter comes in a horizontal left to right configuration. If
a vertical orientation is required then the Magnehelic
®
gage must be
rotated 90° and remounted on bracket.
2. The Magnehelic
®
gage can be mounted remotely from the meter. If
this is done make sure to keep the Magnehelic
®
gage above the Venturi
Flow Tube assembly. Condensation may collect in the tube if it is below
the gage and cause false readings.
3. The Venturi Flow Tube must be connected in the correct orientation.
For example, in a left to right flow, the high pressure side which is on the
left connects to the high pressure port on the Magnehelic
®
gage. The low
pressure side is on the right and connects to the low pressure port of the
Magnehelic
®
gage.
SPECIFICATIONS
Service: Air and non-combustible, compatible gases. (Natural Gas
option available).
Wetted Materials: Aluminum, silicone, acrylic, polycarbonate, high
carbon steel, low carbon steel, brass, paper, acrylic paint, enamel paint,
alkyd coating, nickel plate, zinc plate, helsel FC, 300 series stainless
steel, PTFE, Loctite
®
AV sealant, commercial black rubber, neoprene,
samarium cobalt, nickel alloy steel cover, beryllium copper.
Housing: Die cast aluminum case and bezel, with acrylic cover. Exterior
finish is coated gray to withstand 168 hour salt spray corrosion test.
Accuracy: ± 2.5% FS.
Pressure Limits: -20˝ Hg to 15 psig (-0.677 bar to 1.034 bar); MP
option: 35 psig (2.41 bar). For applications with high cycle rate within
gage total pressure rating, next higher rating is recommended.
Overpressure: Relief plug opens at approximately 25 psig (1.72 kPa).
Temperature Limits: 20 to 140°F (-6.67 to 60°C).
Size: 4˝ (101.6 mm) diameter dial face.
Mounting Orientation: Diaphragm in vertical position. Consult factory
for other position orientations.
Process Connection: Female NPT of nominal line size (from 1˝ to 4˝ ).
Weight: Gage only: 1 lb 2 oz (510 g), MP & HP 2 lb 2 oz (963 g).
Venturi: 1˝: 3 lbs (1.36 kg); 1-1/2˝: 4.5 lbs (2.04 kg); 2˝: 6 lbs (2.72 kg);
3˝: 11 lbs (4.99 kg); 4˝: 18 lbs (8.16 kg).
MAINTENANCE
After final installation of the Venturi Flow Meter with Magnehelic
®
Gage,
no routine maintenance is required. A periodic check of system calibration
is suggested. These devices are not field repairable and should be
returned if repair is needed. Be sure to include a brief description of the
problem plus any relevant application notes. Contact customer service to
receive a return goods authorization number before shipping.
©Copyright 2009 Dwyer Instruments, Inc. Printed in U.S.A. 5/09 FR# R1-443654-00 Rev.2
Note: Loctite® is a registered trademark of Henkel Corporation.
(A)
(F)
(E)
FLOW
(øC)
(B)
(ø4.750)
(D)
90° APPROX.
(G)
(H)
(.500)
(1.250)
(.687)
SIDE PORTS
PLUGGED
GAGE ASSEMBLY IS SHOWN
TO ILLUSTRATE MOUNTING
ORIENTATION WITH THE
VF KIT.
VFLO Kit
VF1
VF2
VF3
VF4
VF5
Line Size
1˝ FNPT
1.5˝ FNPT
2˝ FNPT
3˝ FNPT
4˝ FNPT
A
4.500
6
7.750
11
14.500
B
2.687
2.562
2.562
2.734
2.734
ØC
2
2.500
3
4
5.000
D
2.015
2.625
3.312
4.625
5.172
E
2.125
2.375
2.875
4
5.000
F
3.125
3.375
3.875
5.500
6.500
G
1.359
2
2.703
4
5.328
H
1.125
1.375
1.750
2.375
3.000
J
4.625
5.250
5.750
7
9.250
K
6.375
7.125
7.875
9.625
11.500
F-VFLO:TEMPLATE 5/28/09 10:40 AM Page 1